Only one central earthing point
By Stefan Fassbinder / Published on Fri, 2007-07-13 18:52Always make sure there is one and only one conductive connection between the N conductor and the PA/PE system within a TN-S installation, even when there are several star points from several sources feeding into the system! Otherwise the beneficial effects of a TN-S system are largely made void.